The product mainly consists of a current-carrying conductor, capacitive core, outer sheath, sheds, flange, end fittings and other components.
A test tap is provided on the flange for partial discharge and dielectric dissipation factor measurements. The test tap shall be opened during testing and reliably grounded during normal operation.
Both ends of the product are equipped with equipment terminal connectors.
·GB/T 4109-2022;
·IEC 60137:2017 – Insulated Bushings for Alternating Voltages Above 1000 V
Model: FCRG–X/Y
- F: Composite main insulation
- C: Wall bushing
- R: Capacitive type
- G: Dry-type insulation with silicone rubber external insulation
- X: Rated voltage, in kV
- Y:Rated current, in A
·Dry-type composite capacitive insulation, oil-free, porcelain-free and gas-free.
·Excellent resistance to pollution and moisture.
·Ambient Temperature: -50°C to +50°C
·Altitude: Designed for an installation altitude of 1000 m. For installations above 1000 m, corrections shall be made in accordance with GB 311.
·Pollution Class: Class IV for outdoor applications and Class III for indoor applications.
(Special requirements shall be specified separately.)
·Applicable Rated Voltage Levels: 12 kV, 24 kV, 40.5 kV, 72.5 kV, 126 kV and 252 kV.
·Rated Primary Current: Up to 6300 A.
(Special design is required for rated currents exceeding 4000 A.)
·60-second power frequency withstand voltage test
·Partial discharge measurement
·Dielectric dissipation factor and capacitance measurement
The relevant lead of the capacitive insulation system must be reliably grounded during normal operation.
| Highest Voltage for Equipment (Um), kV | Rated Voltage, kV | Power Frequency Withstand Voltage, kV | Lightning Impulse Withstand Voltage (Peak), kV | Partial Discharge Level at 1.05Um/√3, pC | Dielectric Dissipation Factor | Rated Short-Time Thermal Current, kA | |
|---|---|---|---|---|---|---|---|
| Dry | Wet | ||||||
| 12 | 10 | 28 | 28 | 75 | ≤5 | ≤0.003 | 25Ir |
| 24 | 20 | 50 | 50 | 125 | ≤5 | ≤0.003 | 25Ir |
| 40.5 | 35 | 95 | 80 | 200 | ≤5 | ≤0.003 | 25Ir |
| 72.5 | 66 | 160 (140) | 140 | 350 (325) | ≤5 | ≤0.003 | 25Ir |
| 126 | 110 | 230 (185) | 230 (185) | 550 (450) | ≤5 | ≤0.003 | 25Ir |
| 252 | 220 | 460 (395) | 460 (395) | 1050 (950) | ≤5 | ≤0.003 | 25Ir |
Temperature Rise: Not exceeding 85 K
| Model | Overall Length (L) | Indoor Overall Length (L1) | Indoor Clearance (L2) | Outdoor Clearance (L3) | Max. Outside Diameter (φD1) | Max. Outside Diameter (φD2) | Terminal Dimensions (L5) | Mounting Flange Dimensions | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Circular Flange | Square Flange | Overall Flange Length | Indoor Length | Flange Thickness | Mounting Holes | |||||||||||||||
| L6 | L7 | L8 | L9 | t | n1-φd1 | φD4 | φD3 | L10 | L11 | L4 | L5 | δ | n2-φd2 | |||||||
| FCRG-72.5/630~1250 | 2120 | 1090 | 630 | 720 | 220 | 180 | 80 | 40 | 80 | 40 | 12 | 4-φ14 | 400 | 350 | 400 | 350 | 350 | 250 | 15 | 6-Φ18 |
| FCRG-72.5/1500~2000 | 2170 | 1115 | 630 | 720 | 220 | 180 | 100 | 50 | 100 | 50 | 15 | 4-φ18 | 400 | 350 | 400 | 350 | 350 | 250 | 15 | 6-Φ18 |
| FCRG-72.5/2500 | 2210 | 1135 | 630 | 720 | 220 | 180 | 125 | 60 | 125 | 60 | 20 | 4-φ18 | 400 | 350 | 400 | 350 | 350 | 250 | 15 | 6-Φ18 |
| FCRG-72.5/3150 | 2330 | 1200 | 630 | 720 | 220 | 180 | 112 | 50 | 170 | 50 | 20 | 6-φ18 | 400 | 350 | 400 | 350 | 350 | 250 | 15 | 6-Φ18 |
| FCRG-72.5/4000 | 2350 | 1210 | 630 | 720 | 220 | 180 | 120 | 60 | 135 | 60 | 20 | 8-φ18 | 400 | 350 | 400 | 350 | 350 | 250 | 15 | 6-Φ18 |
| FCRG-126/630~1250 | 3120 | 1500 | 990 | 1110 | 220 | 180 | 80 | 40 | 80 | 40 | 12 | 4-φ14 | 400 | 350 | 400 | 350 | 600 | 300 | 15 | 6-Φ18 |
| FCRG-126/1500~2000 | 3170 | 1525 | 990 | 1110 | 220 | 180 | 100 | 50 | 100 | 50 | 15 | 4-φ18 | 400 | 350 | 400 | 350 | 600 | 300 | 15 | 6-Φ18 |
| FCRG-126/2500 | 3210 | 1545 | 990 | 1110 | 220 | 180 | 125 | 60 | 125 | 60 | 20 | 4-φ18 | 400 | 350 | 400 | 350 | 600 | 300 | 15 | 6-Φ18 |
| FCRG-126/3150 | 3330 | 1605 | 990 | 1110 | 220 | 180 | 112 | 50 | 170 | 50 | 20 | 6-φ18 | 400 | 350 | 400 | 350 | 600 | 300 | 15 | 6-Φ18 |
| FCRG-126/4000 | 3350 | 1615 | 990 | 1110 | 220 | 180 | 120 | 60 | 135 | 60 | 20 | 8-φ18 | 400 | 350 | 400 | 350 | 600 | 300 | 15 | 6-Φ18 |
| FCRG-252/630~2000 | 5450 | 2675 | 1950 | 2050 | 290 | 290 | 100 | 50 | 100 | 50 | 15 | 4-φ18 | 700 | 600 | 700 | 640 | 900 | 450 | 20 | 8-Φ24 |
| FCRG-252/2500 | 5500 | 2700 | 1950 | 2050 | 290 | 290 | 125 | 60 | 125 | 60 | 20 | 4-φ18 | 700 | 600 | 700 | 640 | 900 | 450 | 20 | 8-Φ24 |
| FCRG-252/3150 | 5620 | 2760 | 1950 | 2050 | 290 | 290 | 112 | 50 | 170 | 50 | 20 | 6-φ18 | 700 | 600 | 700 | 640 | 900 | 450 | 20 | 8-Φ24 |
| FCRG-252/4000 | 5640 | 2770 | 1950 | 2050 | 290 | 290 | 120 | 60 | 135 | 60 | 20 | 8-φ18 | 700 | 600 | 700 | 640 | 900 | 450 | 20 | 8-Φ24 |
| Model | Overall Length (L) | Indoor Overall Length (L1) | Indoor Clearance (L2) | Outdoor Clearance (L3) | Max. Outside Diameter (φD1) | Max. Outside Diameter (φD2) | Terminal Dimensions (L5) | |||
|---|---|---|---|---|---|---|---|---|---|---|
| L4 | L5 | t | n1-φd1 | |||||||
| FCRG-12/630~1250 | 955 | 440 | 140 | 215 | 140 | 140 | 80 | 40 | 12 | 4-φ14 |
| FCRG-12/1500~2500 | 1005 | 465 | 140 | 215 | 140 | 140 | 100 | 50 | 15 | 4-φ18 |
| FCRG-12/3150 | 995 | 460 | 140 | 215 | 140 | 140 | 100 | 50 | 15 | 8-φ18 |
| FCRG-12/4000 | 1085 | 505 | 140 | 215 | 140 | 140 | 125 | 60 | 16 | 8-φ18 |
| FCRG-24/630~1250 | 1080 | 480 | 180 | 300 | 140 | 140 | 80 | 40 | 12 | 4-φ14 |
| FCRG-24/1500~2500 | 1130 | 505 | 180 | 300 | 140 | 140 | 100 | 50 | 15 | 4-φ18 |
| FCRG-24/3150 | 1120 | 500 | 180 | 300 | 140 | 140 | 100 | 50 | 15 | 8-φ18 |
| FCRG-24/4000 | 1210 | 545 | 180 | 300 | 140 | 140 | 125 | 60 | 16 | 8-φ18 |
| FCRG-40.5/630~1250 | 1300 | 600 | 300 | 400 | 180 | 180 | 80 | 40 | 12 | 4-φ14 |
| FCRG-40.5/1500~2500 | 1350 | 625 | 300 | 400 | 180 | 180 | 100 | 50 | 15 | 4-φ18 |
| FCRG-40.5/3150 | 1340 | 620 | 300 | 400 | 180 | 180 | 100 | 50 | 15 | 8-φ18 |
| FCRG-40.5/4000 | 1430 | 665 | 300 | 400 | 180 | 180 | 125 | 60 | 16 | 8-φ18 |