The 630A 12/24kV Deadbreak Bushing are designed for Cable Branch Cabinet with Sf6 Switch. Separable connectors, such as 630A T-II deadbreak connectors can be used with these bushing. These bushing are made by Epoxy Resin. With the skirt make the Deadbreak Rotatable Feedthru Bushing can be used better.
Tests conducted in accordance with IEC60502-4 and IEC60137.
-[12kV] Partial discharge minimum extinction voltage -15kV
-[24kV] Partial discharge minimum extinction voltage -20kV
-[12kV] AC 60Hz for 5min(kV crest) - 39kV
-[24kV] AC 60Hz for 5min(kV crest) - 54kV
1.INTERFACE
Type C-630A interface as described by CENELEC EN 50180 and 50181.
2.INSULATOR
An epoxy compound that has excellent electrical, thermal and mechanical properties and is environmentally stable.
3.SCREEN
Screen provide a convenient point to connect drain wire to ensure grounding of the connector shield, or connect potential indicator or fault indicator
- MS
- 12/24-630
- DBIT
| Continuous operating voltage: | 10kV | 20kV |
|---|---|---|
| Maximum Rating Phase-to-Phase: | 12kV | 24kV |
| AC withstand voltage,5min: | 39kV | 54kV |
| DC withstand voltage,15min: | 53kV | 78kV |
| Impulse withstand voltage: | 95kV | 125kV |
| Minimum Corona Voltage Level: | 11kV | 19kV |