The Connecting Plug is molded from high quality insulating epoxy material. It meets all the requirements of the IEC 60137 standard. The interface is Type C, the specifications of standard EN 50181. The Connecting Plug is interchangeable with other manufacturer's products which meet the same standards.
Tests conducted in accordance with IEC60502-4 and IEC60137.
-[12kV] Partial discharge minimum extinction voltage -15kV
-[24kV] Partial discharge minimum extinction voltage -20kV
-[36kV] Partial discharge minimum extinction voltage -45kV
-[12kV] AC 60Hz for 5min(kV crest) - 39kV
-[24kV] AC 60Hz for 5min(kV crest) - 54kV
-[36kV] AC 60Hz for 5min(kV crest) - 117kV
1.INTERFACE
Type C-630A interface as described by CENELEC EN 50180 and 50181.
2.INSULATOR
An epoxy compound that has excellent electrical, thermal and mechanical properties and is environmentally stable.
3.SCREEN
Screen provide a convenient point to connect drain wire to ensure grounding of the connector shield, or connect potential indicator or fault indicator
- MS
- 12/24/36-630
- DCPE
| Continuous operating voltage: | 10kV | 20kV | 36kV |
|---|---|---|---|
| Maximum Rating Phase-to-Phase: | 12kV | 24kV | 40.5kV |
| AC withstand voltage,5min: | 39kV | 54kV | 117kV |
| DC withstand voltage,15min: | 53kV | 78kV | 104kV |
| Impulse withstand voltage: | 95kV | 125kV | 200kV |
| Minimum Corona Voltage Level: | 11kV | 19kV | 26kV |
Minimum Values of Cantilever Withstand Load( N ): 500N