The 200A Class Bushing Well meets the full requirements of IEEE standard.
It is designed for the termination of primary winding leads at the front plate of
fluid-filled apparatus rated at 8.3/14.4kV and 15.2/26.3kV. The bushing well is
externally clamped for sidewall mounting on single-or three-phase transformers filled with transformer oil or an approved equivalent bio-based fluid.
Continuous: 200 amps rms
Switching: 10 operations at 200 amp 10s rms at 14.4kA
Short Time : 10000 Arms symmetrical for 0.17s
3500 Arms symmetrical for 3.0s
1.WELL HOUSE
An epoxy compound that has excellent electrical, thermal andmechanical properties and is environmentally stable.
| Voltage Class | 15kV | 25kV |
|---|---|---|
| Partial discharge minimum extinction voltage | 15kV | 19kV |
| AC 60Hz for 1min(kV crest) | 34kV | 54kV |
| Voltage Class | 15kV | 25kV |
|---|---|---|
| Max. Voltage Rating Phase to Phase | 14.4kV | 26.3kV |
| Max. Voltage Rating Phase to Ground | 8.3kV | 15.2kV |
| AC 60Hz for 1 Minute | 34kV | 54kV |
| DC for 15 Minute | 53kV | 78kV |
| BIL and Full Wave Crest | 95kV | 125kV |
| Partial discharge minimum extinction voltage(< 10pc) | 15kV | 19kV |
| S.Dim | 15kV |
|---|---|
| S1 | 57.5 |
| M1 | 55 |
| M2 | 80 |
| M3 | 64.5 |