The 36kV Apparatus Bushing are designed for European type Cable Branch Cabinet, Power Surrounding Supply Cabinet, Used in European type Cable Branch Cabinet connecting with high voltage and wind power substation. These bushings can connect with the deadbreak cable connector. These bushing are made by Epoxy Resin with good mechanical and electrical properties.
Tests conducted in accordance with IEC60502-4 and IEC 60137.
-Partial discharge minimum extinction voltage-45kV
-AC 60Hz for 5min(kV crest)-117kV
1.INTERFACE
Type C-630A interface as described by CENELEC EN 50180 and 50181.
2.INSULATOR
An epoxy compound that has excellent electrical, thermal and mechanical properties and is environmentally stable.
3.SCREEN
Screen provide a convenient point to connect drain wire to ensure grounding of the connector shield, or connect potential indicator or fault indicator
- MS
- 36-630
- DBI
Minimum Values of Cantilever Withstand Load( N ): 500N
| Continuous operating voltage: | 36kV |
|---|---|
| Maximum Rating Phase-to-Phase: | 40.5kV |
| Maximum Rating Phase-to-ground: | 26kV |
| AC withstand voltage,5min: | 117kV |
| DC withstand voltage,15min: | 106kV |
| Impulse withstand voltage: | 200kV |
| Minimum Corona Voltage Level: | 26kV |