25kV 600A/200A Loadbreak Reducing Tap Plug is used to covert a standard 600A deadbreak interface to a standard 200A loadbreak interface.
Order Information
Description | Reference No. |
25kV 600A/200A Loadbreak Reducing Tap Plug | UG RP-25/600/200 |
Performance
Used with a 200A insulated protective cap, M.O.V Elbow Arrester, grounding elbow or loadbreak elbow connector, a Loadbreak Reducing Tap Plug provides a fully shielded.
Bom
– Loadbreak Reducing Tap Plug
– Two Head Screw
– Cleaning Tissue
– Silicone Lubricant
– Covering Cap
– Installation Instruction Sheet(Optional)
Electrical Characteristics
Voltage Rating | 25kV |
Maximum Rating Phase-to-phase | 26.3kV |
Maximum Rating Phase-to-ground | 15.2kV |
AC 50Hz 1 Minute Withstand | 40kV |
DC 15 Minute Withstand | 78kV |
BIL and 1.5 / 50µs Impulse Withstand Voltage | 125kV |
Partial Discharge Voltage | 19kV ( <3pC) |
Continuous Current | 600A |
24h Overload | 1000A |
Short Time | 50kA rms sym. for 0.3s 20kA rms sym. for 4.0s |
Meets ANSI/IEEE 386, latest version. Mate with bushing interface figure 5 and figure 11. |