15kV 200AMP Loadbreak Bushing Insert

15kV 200A Bushing Insert threads into a universal bushing well to provide the same function as an integral loadbreak bushing. Using bushing inserts makes field installation and replacement possible and efficient. Bushing inserts and elbow connectors comprise the essential components of all loadbreak connections.

Order Information
Description Reference No. Voltage Rating Current Rating
15kV 200A Loadbreak Bushing Insert UG BI-15/200 15kV 200A
Performance

The uncomplicated nature of the current path design delivers superior and reliable performance. An internal broach allows for positive torque controlled installation. Using the optional installation torque tool the bushing insert can be properly tightened into the bushing well without the fear of accidentally breaking the bushing well stud. Power exclusive latch indicator ring, located on the circumference of the bushing’s collar, eliminates the guesswork of loadbreak elbow installation on the bushing insert. The bright yellow ring provides immediate feedback to determine if the elbow is properly installed on the insert. If the yellow ring is completely covered by the loadbreak elbow, it is fully ”latched” if the ring is visible. The elbow can be installed correctly before any problems can occur. The Bushing Inserts are molded with high quality sulfur-cured insulating and semiconducting EPDM rubber.When mated with a comparably rated component, the bushing insert provides a fully shielded and submersible connection for loadbreak operation.

Electrical Characteristics
Voltage Rating 15kV
Maximum Rating Phase-to-phase 14.4kV
Maximum Rating Phase-to-ground 8.3kV
AC 50Hz 1 Minute Withstand 34kV
DC 15 Minute Withstand 53kV
BIL and 1.5 / 50µs Impulse Withstand Voltage 95kV
Partial Discharge Voltage 11kV ( <3pC)
Continuous Current 200A
Switching Current 10 operations at 200A,14.4kV
Fault Closure 10kA
Short Time 10kA rms sym. For 0.17s (60Hz) / 0.2s (50Hz) 3.5kA rms sym. for 3.0s
Meets ANSI / IEEE 386, latest version. Mate with bushing interface figure 5.
Bom

– Loadbreak Bushing Insert

– Cleaning Tissue

– Silicone Lubricant

– Covering Cap

– Grounding Wire

– Installation Instruction Sheet(Optional)