15kV 200AMP Insulated Standoff Bushing

The insulated standoff bushing is designed to be installed in the parking stand mounted on a transformer or other apparatus. It is used together with the cable accessories such as elbow connector elbow surge arrester and the other 200A Loadbreak Accessories. A grounding lug is provided on the standoff bushing bracket for attachment of a drain wire to ensure deadfront construction. When mated with a comparably rated product, the insulated standoff bushing provides a fully-shielded, submersible, separable connector for energized operation.

The standard insulated standoff bushing has a stainless steel eyebolt with a brass pressure foot. The molded EPDM rubber body is bolted to a stainless steel base bracket using a galvanized steel holddown ring. A completely stainless steel bracket assembly is available for extremely corrosive environments.

The insulated standoff bushing is designed to be installed in the parking stand mounted on a transformer or other apparatus. It is used together with the cable accessories such as elbow connector elbow surge arrester and the other 200A Loadbreak Accessories. A grounding lug is provided on the standoff bushing bracket for attachment of a drain wire to ensure deadfront construction. When mated with a comparably rated product, the insulated standoff bushing provides a fully-shielded, submersible, separable connector for energized operation.

The standard insulated standoff bushing has a stainless steel eyebolt with a brass pressure foot. The molded EPDM rubber body is bolted to a stainless steel base bracket using a galvanized steel holddown ring. A completely stainless steel bracket assembly is available for extremely corrosive environments.

 

Order Information
Description Reference No. Voltage Rating Current Rating
15kV 200A Insulated Standoff Bushing UG SB-15/200 15kV 200A

 

Electrical Characteristics
Voltage Rating 15kV
Maximum Rating Phase-to-phase 14.4kV
Maximum Rating Phase-to-ground 8.3kV
AC 50Hz 1 Minute Withstand 34kV
DC 15 Minute Withstand 53kV
BIL and 1.5 / 50µs Impulse Withstand Voltage 95kV
Partial Discharge Voltage 11kV ( <3pC)
Continuous Current 200A
Switching Current 10 operations at 200A,14.4kV
Fault Closure 10kA
Short Time 10kA rms sym. For 0.17s (60Hz) / 0.2s (50Hz) 3.5kA rms sym. for 3.0s
Meets ANSI / IEEE 386, latest version. Mate with bushing interface figure 5.

 

Bom

– Insulated Standoff Bushing

– Covering Cap

– Silicone Lubricant

– Cleaning Tissue

– Installation Instruction Sheet(Optional)

Reviews

There are no reviews yet.

Be the first to review “15kV 200AMP Insulated Standoff Bushing”

Your email address will not be published. Required fields are marked *

Scroll to Top