24kV 630AMP Deadbreak Shielded Sub-Connector

630A Sub-Connector can be used together with the ForeCon nector and some other sub connect. It can be provided more branches, and they can not together with the bushing directly, cover the back protection cap on the end of the blanking cover.

630A Sub-Connector can be used together with the ForeCon nector and some other sub connect. It can be provided more branches, and they can not together with the bushing directly, cover the back protection cap on the end of the blanking cover.

 

Performance

Shielded Fore-Connector provides a fully screened and fully submersible separable connection when mated with the proper bushing or plug. It can be used under the circumstances. Built-in capacitive test point to determine the circuit status or install a fault indicator.No minimum phase clearance requirements. For mounting can be vertical, horizontal, or any angle in between.

 

Order Information

Reference No. Conductor Cross Section (mm²) Stretch Range Over Insulation(mm) Cable Type(kV) Corresponding Code
UG DSS-24/630-35 35 18.3-21.5 12/20(24) B
UG DSS-24/630-50 50 19.9-24.6 12/20(24) C
UG DSS-24/630-70 70 19.9-24.6 12/20(24) C
UG DSS-24/630-95 95 23.1-27.1 12/20(24) D
UG DSS-24/630-120 120 23.1-27.1 12/20(24) D
UG DSF-24/630-150 150 24.9-29.0 12/20(24) E
UG DSS-24/630-185 185 27.4-32.5 12/20(24) F
UG DSS-24/630-240 240 27.4-32.5 12/20(24) F
UG DSS-24/630-300 300 31.0-36.1 12/20(24) G
UG DSS-24/630-400 400 34.5-37.6 12/20(24) H

Any other special requirement, please contact our sales engineer. The adapter code should be confirmed while ordering.

 

Electrical Characteristics

Voltage Rating 24kV
Maximum Rating Phase-to-ground 12kV
AC 50Hz 5 Minute Withstand 54kV
DC 15 Minute Withstand 48kV
BIL Impulse Withstand Voltage 125kV
Partial Discharge Voltage 20kV (< 10pC)
Continuous Current 630A
24h Overload 1000A
Short Time 10kA rms sym. for 0.2s 35kA rms sym. for 3.0s
Meets IEC 60502-4, latest version.

 

Bom

– Sub-Connector

– Covering Cap

– Insulating Plug

– Adaptor

– Conductor Cable Lug

– Threaded Stud

– Connecting Rod

– Silicone Lubricant

– Cleaning Tissue

– Wrench(Optional)

– Grounding Wire(Optional)

– Installation Instruction Sheet(Optional)