24kV 630A Deadbreak Shielded Fore-Connector is for the connection of polymeric cable to transformers, switchgear, motors and other equipment with a premoulded separable connector for indoor and outdoor installations. The system voltage up to 24kV and continuous current is 630A.
Performance
Shielded Fore-Connector provides a fully screened and fully submersible separable connection when mated with the proper bushing or plug. It can be used under the circumstances. Built-in capacitive test point to determine the circuit status or install a fault indicator.No minimum phase clearance requirements. For mounting can be vertical, horizontal, or any angle in between.
Order Information
Reference No. | Conductor Cross Section (mm²) | Stretch Range Over Insulation(mm) | Cable Type(kV) | Corresponding Code |
UG DSF-24/630-35 | 35 | 18.3-21.5 | 12/20(24) | B |
UG DSF-24/630-50 | 50 | 19.9-24.6 | 12/20(24) | C |
UG DSF-24/630-70 | 70 | 19.9-24.6 | 12/20(24) | C |
UG DSF-24/630-95 | 95 | 23.1-27.1 | 12/20(24) | D |
UG DSF-24/630-120 | 120 | 23.1-27.1 | 12/20(24) | D |
UG DSF-24/630-150 | 150 | 24.9-29.0 | 12/20(24) | E |
UG DSF-24/630-185 | 185 | 27.4-32.5 | 12/20(24) | F |
UG DSF-24/630-240 | 240 | 27.4-32.5 | 12/20(24) | F |
UG DSF-24/630-300 | 300 | 31.0-36.1 | 12/20(24) | G |
UG DSF-24/630-400 | 400 | 34.5-37.6 | 12/20(24) | H |
Any other special requirement, please contact our sales engineer. The adapter code should be confirmed while ordering.
Electrical Characteristics
Voltage Rating | 24kV |
Maximum Rating Phase-to-ground | 12kV |
AC 50Hz 5 Minute Withstand | 54kV |
DC 15 Minute Withstand | 48kV |
BIL Impulse Withstand Voltage | 125kV |
Partial Discharge Voltage | 20kV (< 10pC) |
Continuous Current | 630A |
24h Overload | 1000A |
Short Time | 10kA rms sym. for 0.2s 35kA rms sym. for 3.0s |
Meets IEC 60502-4, latest version. Mate with bushing Interface C. |
Bom
– Fore-Connector
– Covering Cap
– Insulating Plug
– Adaptor – Conductor Cable Lug
– Threaded Stud
– Silicone Lubricant
– Installation Tool(Optional)
– Grounding Wire(Optional)
– Installation Instruction Sheet(Optional)