The Insulated Standoff Bushing is designed to be installed in the parking stand mounted on a transformer or other apparatus. It is used together with the cable accessories such as elbow connector, elbow surge arrester and the other 600A Loadbreak Accessories. A grounding lug is provided on the standoff bushing bracket for attachment of a drain wire to ensure dead front construction. When mated with a comparably rated product, the insulated standoff bushing provides a fullyshielded, submersible, separable connector for energized operation. The standard insulated standoff bushing has a stainless steel eyebolt with a btass pressure foot. The molded EPDM rubber body is bolted to a stainless steel base bracket using a galvanized steel holddown ring.
Order Information
Description | Reference No. | Voltage Rating | Current Rating |
15kV 600A Insulated Standoff Bushing | UG SB-15/600 | 15kV | 600A |
25kV 600A Insulated Standoff Bushing | UG SB-25/600 | 25kV | 600A |
Electrical Characteristics
Voltage Rating | 15kV | 25kV |
Maximum Rating Phase-to-phase | 14.4kV | 26.3kV |
Maximum Rating Phase-to-ground | 8.3kV | 15.2kV |
AC 50Hz 1 Minute Withstand | 34kV | 40kV |
DC 15 Minute Withstand | 53kV | 78kV |
BIL and 1.5 / 50µs Impulse Withstand Voltage | 95kV | 125kV |
Partial Discharge Voltage | 11kV ( <3pC) | 19kV ( <3pC) |
Continuous Current | 600A | 600A |
24h Overload | 1000A | |
Short Time | 25kA rms sym. for 0.17s(60Hz)/0.2s(50Hz) 10kA rms sym. for 3.0s | |
Meets ANSI/IEEE 386 , latest version. Mate with bushing interface figure 11. |
Bom
– Insulated Standoff Bushing
– Stainless Steel Mounting Plate
– Covering Cap
– Installation Instruction Sheet(Optional)
Reviews