The Integral Deadreak Bushing combines the advantages of reliable integral design with the operating features required for three-phase switching. The bushing is designed for padmounted transformers, switchgear and other apparatus fliled with transformer oil, or an approved equivalent. It eliminates the insert-to-well interface present in bushing well and insert primary terminations. The Bushing is molded with high quality insulating material. When mated with comparably rated products, it provides a fully shielded, submersible and separable connection for loadbreak operation.
Order Information
Description | Reference No. | Voltage Rating | Current Rating |
15kV 600A Integral Deadbreak Bushing | UG DB-15/600 | 15kV | 600A |
25kV 600A Integral Deadbreak Bushing | UG DB-25/600 | 25kV | 600A |
Electrical Characteristics
Voltage Rating | 15kV | 25kV |
Maximum Rating Phase-to-phase | 14.4kV | 26.3kV |
Maximum Rating Phase-to-ground | 8.3kV | 15.2kV |
AC 50Hz 1 Minute Withstand | 34kV | 40kV |
DC 15 Minute Withstand | 53kV | 78kV |
BIL and 1.5 / 50µs Impulse Withstand Voltage | 95kV | 125kV |
Partial Discharge Voltage | 11kV ( <3pC) | 19kV ( <3pC) |
Continuous Current | 600A | 600A |
24h Overload | 1000A | |
Short Time | 25kA rms sym. for 0.17s(60Hz)/0.2s(50Hz) 10kA rms sym. for 3.0s | |
Meets ANSI/IEEE 386 , latest version. Mate with bushing interface figure 11. |
Bom
– Integral Deadbreak Bushing
– Covering Cap
– Installation Instruction Sheet(Optional)