25kV 600A/200A Loadbreak Reducing Tap Plug

25kV 600A/200A Loadbreak Reducing Tap Plug is used to covert a standard 600A deadbreak interface to a standard 200A loadbreak interface.

 

25kV 600A/200A Loadbreak Reducing Tap Plug is used to covert a standard 600A deadbreak interface to a standard 200A loadbreak interface.

 

Order Information

Description Reference No.
25kV 600A/200A Loadbreak Reducing Tap Plug UG RP-25/600/200

 

Performance

Used with a 200A insulated protective cap, M.O.V Elbow Arrester, grounding elbow or loadbreak elbow connector, a Loadbreak Reducing Tap Plug provides a fully shielded.

 

Bom

– Loadbreak Reducing Tap Plug

– Two Head Screw

– Cleaning Tissue

– Silicone Lubricant

– Covering Cap

– Installation Instruction Sheet(Optional)

 

Electrical Characteristics

Voltage Rating 25kV
Maximum Rating Phase-to-phase 26.3kV
Maximum Rating Phase-to-ground 15.2kV
AC 50Hz 1 Minute Withstand 40kV
DC 15 Minute Withstand 78kV
BIL and 1.5 / 50µs Impulse Withstand Voltage 125kV
Partial Discharge Voltage 19kV ( <3pC)
Continuous Current 600A
24h Overload 1000A
Short Time 50kA rms sym. for 0.3s 20kA rms sym. for 4.0s
Meets ANSI/IEEE 386, latest version. Mate with bushing interface figure 5 and figure 11.