35kV Cold Shrinkage Straight Joint

Cold Shrinkage Straight Joint for single-core/three-core armored or non-armoured XLPE/EPR cables below 35KV.

Category:

Cold Shrinkage Straight Joint for single-core/three-core armored or non-armoured XLPE/EPR cables below 35KV.

Material performance test
Test Items Test Method Test Requirements
Tensile strength ASTM D 638 9.5MPa Min
Ultimate elongation ASTM D 638 850% Min
Tear Strength ASTM D 638 24KN/m Min
Density ASTM D 792 1.2g/cm³
Performance test
Voltage 6/10(12)kV 8.7/15(17.5)kV 12/20(24)kV 18/30(36)kV
Partial discharge test at room temperature 10kV, <5pC 15kV, <5pC 20kV, <5pC 30kV, <5pC
power-frequency voltage test 27kV 5min 39kV 5min 54kV 5min 81kV 5min
impulse voltage test 75kV ± 10 times 95kV ± 10 times 125kV ± 10 times 170kV ± 10 times

 

Dimensions
6/10(12)kV
Model Cable insulation OD(mm) Cross section(mm²)
UG-CSJ-10kV-1 16.5-19.7 70-95
UG-CSJ-10kV-2 19.7-23.5 120-150
UG-CSJ-10kV-3 22.5-31.3 185-300
UG-CSJ10kV-4 28.9-38.0 400-630
8.7/15(17.5)kV
Model Cable insulation OD(mm) Cross section(mm²)
UG-CSJ-17.5kV-1 16.5-19.7 25-50
UG-CSJ-17.5kV-2 19.7-23.5 70-120
UG-CSJ-17.5kV-3 22.5-31.3 150-300
UG-CSJ-17.5kV-4 28.9-38.0 400-500
12/20(24)kV
Model Cable insulation OD(mm) Cross section(mm²)
UG-CSJ-24kV-1 19.7-23.5 35-50
UG-CSJ-24kV-2 22.5-31.3 70-150
UG-CSJ-24kV-3 28.9-38.0 185-400
UG-CSJ-24kV-4 38.0-44.1 500-630
18/30(36)kV
Model Cable insulation OD(mm) Cross section(mm²)
UG-CSJ-36kV-1 25.9-33.9 50-150
UG-CSJ-36kV-2 33.7-41.3 185-300
UG-CSJ-36kV-3 41.3-47.0 400-500
UG-CSJ-36kV-4 47.0-53.5 630