Cold Shrinkage Straight Joint for single-core/three-core armored or non-armoured XLPE/EPR cables below 35KV.
Material performance test
Test Items |
Test Method |
Test Requirements |
Tensile strength |
ASTM D 638 |
9.5MPa Min |
Ultimate elongation |
ASTM D 638 |
850% Min |
Tear Strength |
ASTM D 638 |
24KN/m Min |
Density |
ASTM D 792 |
1.2g/cm³ |
Performance test
Voltage |
6/10(12)kV |
8.7/15(17.5)kV |
12/20(24)kV |
18/30(36)kV |
Partial discharge test at room temperature |
10kV, <5pC |
15kV, <5pC |
20kV, <5pC |
30kV, <5pC |
power-frequency voltage test |
27kV 5min |
39kV 5min |
54kV 5min |
81kV 5min |
impulse voltage test |
75kV ± 10 times |
95kV ± 10 times |
125kV ± 10 times |
170kV ± 10 times |
Dimensions
6/10(12)kV |
Model |
Cable insulation OD(mm) |
Cross section(mm²) |
UG-CSJ-10kV-1 |
16.5-19.7 |
70-95 |
UG-CSJ-10kV-2 |
19.7-23.5 |
120-150 |
UG-CSJ-10kV-3 |
22.5-31.3 |
185-300 |
UG-CSJ10kV-4 |
28.9-38.0 |
400-630 |
8.7/15(17.5)kV |
Model |
Cable insulation OD(mm) |
Cross section(mm²) |
UG-CSJ-17.5kV-1 |
16.5-19.7 |
25-50 |
UG-CSJ-17.5kV-2 |
19.7-23.5 |
70-120 |
UG-CSJ-17.5kV-3 |
22.5-31.3 |
150-300 |
UG-CSJ-17.5kV-4 |
28.9-38.0 |
400-500 |
12/20(24)kV |
Model |
Cable insulation OD(mm) |
Cross section(mm²) |
UG-CSJ-24kV-1 |
19.7-23.5 |
35-50 |
UG-CSJ-24kV-2 |
22.5-31.3 |
70-150 |
UG-CSJ-24kV-3 |
28.9-38.0 |
185-400 |
UG-CSJ-24kV-4 |
38.0-44.1 |
500-630 |
18/30(36)kV |
Model |
Cable insulation OD(mm) |
Cross section(mm²) |
UG-CSJ-36kV-1 |
25.9-33.9 |
50-150 |
UG-CSJ-36kV-2 |
33.7-41.3 |
185-300 |
UG-CSJ-36kV-3 |
41.3-47.0 |
400-500 |
UG-CSJ-36kV-4 |
47.0-53.5 |
630 |