24kV 250AMP Deadbreak Plug-in Bushing

24kV 250A Deadbreak Bushing provides the interface for the 250A Cable Connector and mostly used on the oil-insulated (R-temp, hydrocarbon, or silicon) apparatus, including switchgear, transformers and capacitors.

24kV 250A Deadbreak Bushing provides the interface for the 250A Cable Connector and mostly used on the oil-insulated (R-temp, hydrocarbon, or silicon) apparatus, including switchgear, transformers and capacitors.

 

Order Information
Description Reference No. Voltage Rating Current Rating
24kV 250A Deadbreak Plug-in Bushing UG DB-24/250 24kV 250A
Electrical Characteristics
Voltage Rating 24kV
Maximum Rating Phase-to-ground 12kV
AC 50Hz 5 Minute Withstand 54kV
DC 15 Minute Withstand 48kV
BIL Impulse Withstand Voltage 125kV
Partial Discharge Voltage 20kV (< 10pC)
Continuous Current 250A
Short Time 10kA rms sym. for 0.2s 35kA rms sym. for 3.0s
Meets IEC 60502-4, latest version. Mate with bushing Interface A.
Bom

– Deadbreak Plug-in Bushing

– Covering Cap

– Seal Ring

– Pressing Plate

– Installation Instruction Sheet(Optional)